The reliable operation of distribution systems is critically dependent on detailed understanding of load impacts on distribution transformer insulation systems. This paper estimates thei mpact of rooftop photovoltaic (PV) generation on a typical 200-kVA, 22/0.415-kV distribution transformer life under different operating conditions. This transformer supplies a suburban area with a high penetration of roof top photovoltaic systems. The transformer loads and the phase distribution of the PV systems are significantly unbalanced. Oil and hot-spot temperature and remnant life of distribution transformer under different PV and balance scenarios are calculated. It is shown that PV can significantly extend the transformer life.

History

Volume

29

Issue

3

Start Page

1212

End Page

1220

Number of Pages

9

ISSN

0885-8977

Location

United States

Publisher

IEEE

Language

en-aus

Peer Reviewed

  • Yes

Open Access

  • No

External Author Affiliations

Power and Energy Centre; Queensland University of Technology; School of Engineering and Technology (2013- ); TBA Research Institute;

Era Eligible

  • Yes

Journal

IEEE transactions on power delivery.